Products
Current Location: Home > Products

Name:LN2-40.5 Iindoor SF6 circuit breaker

Overview:

• Classification Series :Indoor Vacuum Circuit Breaker

• Product Name :LN2-40.5 Iindoor SF6 circuit breaker

• Product Overview
LN2-40.5 indoor SF6 circuit breaker is an indoor device designed for use in 50 Hz three-phase AC systems. It is suitable for industrial enterprises, power plants, and substations for protection and control purposes and can be used in locations...


Service
LN2-40.5 Iindoor SF6 circuit breaker
Product Introduction

▸ Product Introduction

Product Introduction

The LN2-40.5 indoor SF6 circuit breaker is an indoor device designed for use in 50 Hz three-phase AC systems. It is suitable for industrial enterprises, power plants, and substations for protection and control purposes and can be used in locations requiring frequent operations. It can also be used as a link circuit breaker and for switching capacitor banks.

The LN2-40.5 model is equipped with the CT10-A spring operating mechanism but can also be paired with the CD101G electromagnetic operating mechanism.


Main Technical Parameters of Circuit Breaker(Model: LN2-40.5/1250A-25

No.

Parameter Name

Unit

Parameter Value

1

Rated voltage

kV

40.5

2

Maximum working voltage

kV

40.5

3

Rated insulation level

kV

185 (lightning impulse, full wave) /
95 (power frequency, 1 min)

4

Rated frequency

Hz

50

5

Rated current

A

1250

6

Rated short-circuit breaking current

kA

25

7

Rated operating sequence

O—0.35s—CO—180s—CO*

8

Rated short-circuit making current (peak)

kA

63

9

Rated dynamic stability current (peak)

kA

63

10

Rated thermal stability current

kA

25

11

Rated thermal stability duration

s

4

12

Switching current for a single capacitor bank

A

400

13

Rated out-of-step breaking current

kA

6.3

14

Accumulated breaking times (rated current)

Times

2000

15

Accumulated breaking times (rated short-circuit)

Times

16

16

Mechanical life



– With CT10-A spring mechanism

Times

6000

– With CD10IIG electromagnetic mechanism

Times

5000

17

Closing time



– Spring mechanism

s

≤0.15

– Electromagnetic mechanism

s

≤0.2

18

Inherent opening time (rated voltage)



– Minimum operating voltage

s

≤0.10

– Maximum operating voltage

s

≤0.07

19

SF6 gas rated pressure (20℃ gauge)

MPa

0.65

20

SF6 gas alarm pressure (20℃ gauge)

MPa

0.42

21

SF6 gas lock pressure (20℃ gauge)

MPa

0.4

22

SF6 gas annual leakage rate

-->
Contact Information
  • Tel.:Manager Zheng:15319942044
  • Tel.:Manager Jin:18291881166
  • Email:service2@hwtmtrade.cn
    service1@hwtmtrade.cn
  • Location:Building 4, Enterprise No.1 Community, Yinshi Military Civilian Integration Industrial Park, No. 333 Yingbin Road, National Aviation High tech Industrial Base, Xi'an City, Shaanxi Province
Scan to follow the official official account Heweitongmao (Shaanxi) Import & Export Trade Co., Ltd.
15319942044 18291881166
Heweitongmao (Shaanxi) Import & Export Trade Co., Ltd.