• Classification Series :Indoor Vacuum Circuit Breaker
• Product Name :ZN28-12 Indoor Vacuum Circuit Breaker
• Product Overview:
Auxiliary power protection for incoming/outgoing lines of 12kV distribution system, distribution stations of industrial and mining enterprises and power plants (suitable for switchgear such as KYN28A-12 and XGN2-12)...
Model meaning
Z: Vacuum Interruption
N: Indoor installation (indoor)
28: Design serial number
12: Rated voltage (kV)
Core function
Full current interrupting: safely interrupt rated current, overload current and short circuit current (up to 31.5kA).
Quick protection: the opening time is ≤60ms, and the fault current is cut off.
Typical application
Auxiliary power protection for incoming/outgoing lines of 12kV distribution system, distribution stations of industrial and mining enterprises and power plants (suitable for switchgear such as KYN28A-12 and XGN2-12).
Selection formula
Short-circuit verification: the expected short-circuit current of the system is less than or equal to the rated breaking current (Isc) of the circuit breaker.
Continuous current: maximum load current × 1.2 ≤ rated current (Ir)
Altitude correction: When it is more than 1000m, the volume of Ir decreases by 1% for every 100m increase.
Mechanical characteristic monitoring
Key indicators: opening speed (1.2 0.2m/s) and overtravel (4±0.5mm).
Abnormal threshold: speed drop > 15% or overtravel < 3mm → overhaul immediately.
Periodic maintenance
3 years /3000 operations:
Measure the resistance of the main circuit (standard: ≤45μΩ @ 1250A)
Check the contact wear (allowable wear ≤3mm)
10 years: replace the vacuum interrupter (compulsory scrapping cycle)
Safety specification
When operating, it must be in the test position/working position, and it is forbidden to open and close in the intermediate state.