Name:BGZ35(Z3)-40.5 Indoor high voltage AC vacuum circuit breaker

Overview:

• Classification Series :Wind-Light Storage Circuit Breaker

• Product Name :BGZ35(Z3)-40.5 Indoor high voltage AC vacuum circuit breaker

• Product Overview
BGZ35(Z3)-40.5 series integrated indoor high-voltage AC vacuum circuit breakers are independently designed and developed by our company according to GB1984, GB/T11022, GB311.1, DL/T593, DL/T402 and other related standards, and have a new generation of 40.5kV...


Service
BGZ35(Z3)-40.5 Indoor high voltage AC vacuum circuit breaker
Product Introduction

▸ Product Introduction

Product overview

BGZ35(Z3)-40.5 series integrated indoor high-voltage AC vacuum circuit breakers are independently designed and developed by our company according to GB1984, GB/T11022, GB311.1, DL/T593, DL/T402 and other related standards, and have a new generation of 40.5kV indoor high-voltage AC vacuum circuit breakers with isolation and grounding. This product has perfect functions, stable and reliable mechanical properties, and is suitable for relatively harsh environments such as high altitude and salt fog at the seaside. It can be widely used in projects such as wind power generation, photovoltaic power generation, energy storage power station, urban distribution network, etc. It has perfect mechanical and electrical interlocking devices, and has extremely high operational reliability and service life. It can complete the safe power distribution function with corresponding switchgear to ensure the safety of operators and equipment.


Product features

The integrated design of isolating switch, breaker switch and grounding switch is a miniaturized high-voltage vacuum circuit breaker with obvious isolation fracture, and the "five-prevention" interlock is simple and reliable;

Contact copper parts adopt cold extrusion molding process, which has good strength and low resistance;

Incoming and outgoing line insulation pillars can be equipped with sensors with live display;

Miniaturization design of circuit breaker and installation in high voltage chamber of box transformer can save most of the cost of cabinet and reduce the overall cost of box transformer.


Environmental conditions of use

1.The altitude is ≤ 3,800 meters;

2.Ambient temperature: -50℃~+50℃,

3.Relative humidity: the mouth average value is not more than 95%, and the monthly average value is not more than 90%;

4.The surrounding air is not obviously polluted by dust, smoke, corrosive and/or combustible gas, steam or salt spray;

5.Places without fire and explosion hazards;

6.The earthquake intensity does not exceed 8 degrees; Places with an inclination not exceeding 5.

Note: The above are the general use conditions of GBTT11022. If the special use environment conditions are high altitude, thick salt fog and extremely cold and hot environment, the technical design can be changed and customized according to the above requirements.


Technical parameter

Parameter

Unit

Standard value

limit value

Rated voltage (Ur)

kV

40.5

-

Rated current (Ir)

A

1250 / 1600 / 2000 / 2500 / 3150

4000 (customized)

Rated short-circuit breaking current (Isc)

kA

25 / 31.5 / 40

50 (Z3 enhanced)

Rated short-term withstand current (4s)

kA

= Isc

-

Rated peak withstand current

kA

63 / 80 / 100

125

Dielectric level




Power frequency withstand voltage (1min)

kV

95 (alternate)/ 118 (fracture)

-

Lightning impulse withstand voltage (peak value)

kV

185 (alternate) / 215 (fracture)

-

Mechanical properties




Opening time

ms

≤ 45

-

Closing time

ms

≤ 80

-

On-off time

ms

≤ 60

-

Mechanical life

≥ 30,000 (Z3)

-

Rated current electrical life

≥ 10,000

-

Full capacity breaking times

≥ 50 (Isc=40kA)

-


Core functions

Full current interrupting: safely interrupting rated current, overload current and short-circuit fault current (the core is different from load switch).

Protection linkage: cooperate with relay protection device to realize automatic protection such as line quick break and overcurrent.


Typical scenario

40.5kV substation inlet/outlet protection, main distribution system of large industrial and mining enterprises, and grid-connected protection cabinets of new energy booster stations (such as KYN61 and GBC-40.5 cabinets).



Contact Information
  • Tel.:Manager Zheng:15319942044
  • Tel.:Manager Jin:18291881166
  • Email:service2@hwtmtrade.cn
    service1@hwtmtrade.cn
  • Location:Building 4, Enterprise No.1 Community, Yinshi Military Civilian Integration Industrial Park, No. 333 Yingbin Road, National Aviation High tech Industrial Base, Xi'an City, Shaanxi Province
Scan to follow the official official account Heweitongmao (Shaanxi) Import & Export Trade Co., Ltd.
15319942044 18291881166
Heweitongmao (Shaanxi) Import & Export Trade Co., Ltd.